Browse Categories

HW R7795C1007

FSG Control

Primary Control, Interrupted Pilot Ultraviolet

Product Info

Commercial/Industrial Electromechanical Burner Controls

R7795 Primary Control

  • Provides solid state, electronic flame safeguard protection
    for commercial and industrial single or dual fuel burners
  • Includes flame signal amplifiers that are color-coded -
    purple for ultraviolet and green for rectification
  • Requires a plug-in prepurge timers of
    1.5, 7, 10, 30, 60 or 90 seconds
  • Mount on a Q795A Wiring subbase with two captive screws
  • Includes line voltage airflow switch to prove air flow from the
    start of prepurge through the run period
  • Prevents start-up with lockout if flame or a flame simulating failure exists
  • Required components: ST795 Prepurge Timer and Q795 Wiring Subbase
  • Frequency: 50/60Hz
  • Temperature range: -40° to 135°F (-40° to 57°C) @ 50Hz
    -20° to 115°F (-29° to 46°C) @ 60 Hz
  • Factory Mutual Approved
  • UL Listed, CSA certified

(a) Safety switch timing: Electronic - 10 seconds, Mechanical - 15 seconds