HW RA890G-1260
Primary Control, Protectorelay 3.0 Response 15 sec Switch Ti
Product Info
Commercial/Industrial Electromechanical Burner Controls
RA890G Protectorelay Primary Control - Ultraviolet Flame Detection
- Primary control provides solid state, electronic flame safeguard protection
for industrial and commercial single or dual fuel burners applications
using Ultraviolet flame detectors - Design for interrupted ignition with intermittent pilot on gas burners,
and interrupted or intermittent ignition on oil burners - Use with a C7027, C7035 or C7044 Minipeeper Ultraviolet Flame Detector
for flame sensing - Recycles if flame signal lost while in Run
- Failure to establish pilot results in a lockout
- Safe-start check prevents start-up if flame-simulating failure
occurs in flame detector circuit - Includes SPDT alarm contacts
- Solid state circuitry, eliminates warm-up and increases resistance to vibration
- Mounting base is made of strong thermoplastic
- Mounts and removes through use of captive mounting screws
- Frequency: 50/60Hz
- Temperature range: -20° to 105°F (-29° to 41°C) @ 50Hz
-20° to 115°F (-29° to 46°C) @ 60 Hz - Factory Mutual Approved
- UL Listed 120V models only, CSA certified
Item Specifications
-
SPDT
-
5" x 5" x 4-3/4"
-
3
-
50/60Hz
-
16 Sec
-
Protectorelay
-
120V