Browse Categories

HW S8610U-3009


Supplier Part #: S8610U3009/U
852672683636

Pilot Module, Univ Intermittent Pilot 1 or 2 Rod Continuous

Product Info

Ignition Pilot Modules

S8610U Universal Intermittent Pilot Module

  • Replaces over 400 multiple field-installed intermittent pilot modules supplied
    by Honeywell®, Robertshaw®, Johnson®, and UTEC® (HSC)
  • Uses existing intermittent pilot burner
  • Includes cross reference, instructions, and accessories for easy replacement
  • Provides ignition sequencing, flame monitoring and safety shutoff for
    intermittent pilot warm air furnaces and heating appliances
  • For use in systems with combination igniter-sensor (single rod or dual rod sense)
  • Provides 100% pilot gas shutoff if pilot fails to light; after 6-minute delay,
    trial for ignition is repeated
  • Ignition trial/delay sequence is repeated until the appliance
    lights or call for heat is removed
  • Honeywell VR8204, VR8304 or VR8345M combination gas control recommended
  • Functional equivalent of S86, S8600, S8610 and S90 modules
  • For use with natural or liquid propane gas
  • Includes spark cable adapters to allow field replacement of both Honeywell® and
    competitive controls without replacing existing spark cable
  • Includes damper connection and automatic vent damper plug
  • CSA Certified


View Accessories

HW 394800-30/U
Ignition Cable, 30" Assembly for S8600 Right Angle Boot

Item Specifications

  • 5 Min
  • 3-15/16" x 5-7/16" x 2-5/8"
  • 1- or 2-Rod
  • 60Hz
  • LP
  • NG
  • 15 or 90 Sec
  • Continuous
  • Intermittent Ignition
  • Damper Connection w/Auto Vent Damper Plug
  • 0 Sec or 30
  • 24V
  • 0.80 lbs per EA